{"id":7663,"date":"2026-02-17T23:58:01","date_gmt":"2026-02-17T15:58:01","guid":{"rendered":"https:\/\/aquarainwater.com\/?p=7663"},"modified":"2026-03-28T00:15:44","modified_gmt":"2026-03-27T16:15:44","slug":"how-does-attenuation-tank-work","status":"publish","type":"post","link":"https:\/\/aquarainwater.com\/fr\/how-does-attenuation-tank-work\/","title":{"rendered":"Comment fonctionne un r\u00e9servoir d'att\u00e9nuation : M\u00e9canisme, contr\u00f4le du d\u00e9bit et dimensionnement UK"},"content":{"rendered":"\n<h1 class=\"wp-block-heading\">How an Attenuation Tank Works: Mechanism, Flow Control and UK Sizing<\/h1>\n\n\n\n<p class=\"has-small-font-size\">By AQUA Rain Water Solutions | February 17, 2026 | 13 min read<\/p>\n\n\n\n<div class=\"wp-block-uagb-image aligncenter uagb-block-a1b2c3d4 wp-block-uagb-image--layout-default wp-block-uagb-image--effect-static wp-block-uagb-image--align-center\"><figure class=\"wp-block-uagb-image__figure\"><img decoding=\"async\" srcset=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-2-1024x546.png ,https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-2.png 780w, https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-2.png 360w\" sizes=\"auto, (max-width: 480px) 150px\" src=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-2-1024x546.png\" alt=\"Cutaway diagram showing how an attenuation tank works underground with geocellular modules, water flow arrows, and flow control device\" class=\"uag-image-8265\" width=\"2400\" height=\"1279\" title=\"how-does-attenuation-tank-work\" loading=\"lazy\" role=\"img\"\/><\/figure><\/div>\n\n\n\n<p>Three months in, the car park is flooded. The drainage had been signed off, the contractor has gone, and the developer has a call from the <strong>LLFA<\/strong> asking why surface water is backed up into the highway drain. Usually, the problem is a poorly designed or undersized <strong>attenuation tank<\/strong>.<\/p>\n\n\n\n<p>Underneath the ground, an <strong>attenuation tank<\/strong> will temporarily store surface water runoff during a heavy storm and then release it slowly at a controlled rate, allowing downstream drains and watercourses to keep up. The UK requirement for new developments \u2014 set out in <strong>CIRIA C753<\/strong> (2015) and Building Regulations Approved Document H (2010) \u2014 is to limit discharge to a greenfield runoff rate, typically ranging from 2 to 8 litres per second per hectare. That single requirement means the attenuation tank exists in new UK drainage systems, and it\u2019s the reason why getting the design right matters more than getting it cheap.<\/p>\n\n\n\n<p>This guide explains how a stormwater attenuation tank really works: from its three-stage storage mechanism to flow control options and UK sizing, material selection and the common failures that can lead to problems.<\/p>\n\n\n\n<p>If you\u2019re new to the topic, it helps to first understand <a href=\"\/blog\/what-is-an-attenuation-tank\/\">what an attenuation tank actually is<\/a> before working through the mechanism in detail.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">How Water Flows Through an Attenuation Tank<\/h2>\n\n\n\n<div class=\"wp-block-uagb-image aligncenter uagb-block-e5f6a7b8 wp-block-uagb-image--layout-default wp-block-uagb-image--effect-static wp-block-uagb-image--align-center\"><figure class=\"wp-block-uagb-image__figure\"><img decoding=\"async\" srcset=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-three-stage-mechanism-2-1024x559.png ,https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-three-stage-mechanism-2-scaled.png 780w, https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-three-stage-mechanism-2-scaled.png 360w\" sizes=\"auto, (max-width: 480px) 150px\" src=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-three-stage-mechanism-2-1024x559.png\" alt=\"\" class=\"uag-image-8266\" width=\"2816\" height=\"1536\" title=\"how-does-attenuation-tank-work-three-stage-mechanism\" loading=\"lazy\" role=\"img\"\/><\/figure><\/div>\n\n\n\n<p>Let\u2019s think of it as a bathtub. The tap is rainfall, whatever rate the sky sends. The drain is the <strong>flow control<\/strong> at the outlet, and that dictates how fast water leaves. Inflow &gt; outflow, the bathtub fills. That\u2019s attenuation in a nutshell.<\/p>\n\n\n\n<p>In reality, there are three phases.<\/p>\n\n\n\n<p>Phase 1: Inflow &amp; energy dissipation. Surface water runoff from roofs, car parks, driveways flows into the tank via the pipe network. At the inlet, the incoming flow is slowed by an energy dissipation device (or inlet manifold). Bypass that and the force of the incoming water scours the inside of the <strong>geocellular<\/strong> crates, dislodging joints and creating debris that clogs up the system.<\/p>\n\n\n\n<p>Phase 2: Storage &amp; head buildup. The <strong>flow control<\/strong> at the outlet limits the discharge to, say, 5 l\/s. Water collects in the void space between the geocellular modules, the water level (hydraulic head) rises. There is hydrostatic pressure against the <strong>flow control<\/strong> which determines how fast water discharges. With a 95% <strong>void ratio<\/strong>, a 100 m\u00b3 excavation gives roughly 95 m\u00b3 of gross storage \u2014 apply a siltation and freeboard deduction in practice.<\/p>\n\n\n\n<p>Phase 3: Controlled release. The storm is over. Inflow drops to zero. The water stored in the void drains out through the flow control, taking longer as head decreases. The tank empties in hours, sometimes days, and is ready for the next rainfall event.<\/p>\n\n\n\n<p>The hydrograph tells it all. An uncontrolled catchment yields a sharp peak flow spike. The <strong>attenuation tank<\/strong> spreads that same volume over a longer period, flattening the peak. That\u2019s the goal.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-style-default is-layout-flow wp-block-quote-is-layout-flow\">\n<p><em><strong>Pro Tip:<\/strong> When modelling in MicroDrainage or similar software, don\u2019t just model the 1-in-100-year storm. Model storms with duration ranging from 15 minutes to 48 hours. Find the critical storm \u2014 the duration that yields the maximum storage demand. It\u2019s usually a 6-hour storm that governs the tank size, not the short intense burst most people assume.<\/em><\/p>\n<\/blockquote>\n\n\n\n<h2 class=\"wp-block-heading\">Vortex Flow Control vs Orifice Plate for Attenuation Tanks<\/h2>\n\n\n\n<div class=\"wp-block-uagb-image aligncenter uagb-block-c9d0e1f2 wp-block-uagb-image--layout-default wp-block-uagb-image--effect-static wp-block-uagb-image--align-center\"><figure class=\"wp-block-uagb-image__figure\"><img decoding=\"async\" srcset=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-vortex-vs-orifice-1-1024x559.png ,https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-vortex-vs-orifice-1-scaled.png 780w, https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-vortex-vs-orifice-1-scaled.png 360w\" sizes=\"auto, (max-width: 480px) 150px\" src=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-vortex-vs-orifice-1-1024x559.png\" alt=\"\" class=\"uag-image-8267\" width=\"2816\" height=\"1536\" title=\"how-does-attenuation-tank-work-vortex-vs-orifice\" loading=\"lazy\" role=\"img\"\/><\/figure><\/div>\n\n\n\n<p>All <strong>attenuation tanks<\/strong> need a <strong>flow control<\/strong> device to control the outflow. Two competing technologies dominate the UK market and the choice will affect tank size, maintenance and cost of ownership.<\/p>\n\n\n\n<p>The orifice plate is the old-timer. It\u2019s a metal plate with a hole. The flow rate is proportional to the square root of head \u2014 it increases as the tank fills then decreases rapidly as the tank discharges. Simple. But here\u2019s the problem. For low discharges below 5 l\/s at burial depths less than 0.6 m, the aperture size will be less than 50 mm. Openings that small get plugged with leaves, grit and construction mud.<\/p>\n\n\n\n<p>The vortex flow control (VFC) \u2014 branded products like Hydro-Brake \u2014 uses a different principle. At low flow water passes through unimpeded. At high head, the tangential entry forces water into rotation generating an air core at the centre. The fluid brake creates resistance but the outlet is approximately 6x larger than the equivalent orifice for the same design flow rate.<\/p>\n\n\n\n<p>VFC tanks can reduce required storage volume by 15 to 30 per cent. The cost savings is on excavation and <strong>geocellular<\/strong> crate quantity.<\/p>\n\n\n\n<figure class=\"wp-block-table is-style-stripes\"><table class=\"has-fixed-layout\"><thead><tr><th>Dimension<\/th><th>Orifice Plate<\/th><th>Vortex Flow Control<\/th><\/tr><\/thead><tbody><tr><td>Clog risk<\/td><td>Very high (small aperture at low flows)<\/td><td>Low (large aperture, self-cleaning action)<\/td><\/tr><tr><td>Hydraulic performance<\/td><td>Standard, flow decays as head drops<\/td><td>Optimised S-curve, higher average discharge<\/td><\/tr><tr><td>Initial cost<\/td><td>Low (\u00a380 to \u00a3200)<\/td><td>Medium to high (\u00a3800 to \u00a32,500)<\/td><\/tr><tr><td>Maintenance<\/td><td>Frequent manual clearing required<\/td><td>Passive, mainly inspection-based<\/td><\/tr><tr><td>Storage volume impact<\/td><td>Baseline<\/td><td>Reduces required volume by 15 to 30%<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<blockquote class=\"wp-block-quote is-style-default is-layout-flow wp-block-quote-is-layout-flow\">\n<p><em><strong>Pro Tip:<\/strong> For residential schemes less than 5 m\u00b3, a simple orifice plate of \u00a380 to \u00a3200 is usually sufficient. For commercial schemes over 0.5 ha, a VFC is almost always worth the premium because the storage reduction alone pays for it. See the <a href=\"\/attenuation-tank-complete-guide-uk\/\">complete guide to attenuation tanks in the UK<\/a> for full specification details.<\/em><\/p>\n<\/blockquote>\n\n\n\n<h2 class=\"wp-block-heading\">How Does an Attenuation Tank Affect Your Drainage Design?<\/h2>\n\n\n\n<div class=\"wp-block-uagb-image aligncenter uagb-block-f1a2b3c4 wp-block-uagb-image--layout-default wp-block-uagb-image--effect-static wp-block-uagb-image--align-center\"><figure class=\"wp-block-uagb-image__figure\"><img decoding=\"async\" srcset=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-geocellular-vs-concrete-2.jpg ,https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-geocellular-vs-concrete-2.jpg 780w, https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-geocellular-vs-concrete-2.jpg 360w\" sizes=\"auto, (max-width: 480px) 150px\" src=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-geocellular-vs-concrete-2.jpg\" alt=\"Geocellular polypropylene attenuation modules stacked on construction site next to precast concrete tank sections showing scale and weight differences\" class=\"uag-image-8268\" width=\"768\" height=\"1024\" title=\"how-does-attenuation-tank-work-geocellular-vs-concrete\" loading=\"lazy\" role=\"img\"\/><\/figure><\/div>\n\n\n\n<p><strong>Step 1: BRE 365 percolation test.<\/strong> Per Part H (2010) of the Building Regulations, there is a drainage hierarchy: infiltration first, watercourse second, and sewer as a last resort. You cannot dismiss infiltration without proving it won\u2019t work. <a href=\"https:\/\/www.bre.co.uk\/page.jsp?id=2858\" target=\"_blank\" rel=\"noopener\">BRE 365 (BRE Digest 365)<\/a> prescribes a programme: dig a trial pit, fill it, note the drop in water level. Without that test result, <strong>LLFA<\/strong>s will send your application back.<\/p>\n\n\n\n<p><strong>Step 2: Greenfield runoff rate.<\/strong> Your attenuation facility can release water no faster than the greenfield runoff rate for the site. Two approaches are available in UK practice. IH124 uses the older WRAP soil maps to compute Qbar. The Flood Estimation Handbook (FEH) uses finer digital soil data (BFIHOST) to compute Qmed. <strong>LLFA<\/strong>s increasingly prefer the FEH. In practice a minimum discharge floor of 2 to 3 l\/s per hectare applies to keep the flow control aperture reliably large enough.<\/p>\n\n\n\n<p><strong>Step 3: Climate change allowances.<\/strong> Per the <a href=\"https:\/\/www.gov.uk\/guidance\/flood-risk-assessments-climate-change-allowances\" target=\"_blank\" rel=\"noopener\">Environment Agency\u2019s guidance on climate change allowances<\/a> (updated 2022), you\u2019re not designing for current rainfall. Storage needs to incorporate uplift factors varying by epoch and sensitivity.<\/p>\n\n\n\n<figure class=\"wp-block-table is-style-stripes\"><table class=\"has-fixed-layout\"><thead><tr><th>Epoch<\/th><th>Central Allowance<\/th><th>Upper End Allowance<\/th><th>Typical Application<\/th><\/tr><\/thead><tbody><tr><td>2050s (2022 to 2060)<\/td><td>+20%<\/td><td>+35%<\/td><td>Commercial, 30 to 50 year design life<\/td><\/tr><tr><td>2070s (2061 to 2125)<\/td><td>+25%<\/td><td>+40 to 45%<\/td><td>Residential, 100 year design life<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p>The drainage hierarchy is set out in full in <a href=\"https:\/\/www.gov.uk\/government\/publications\/drainage-and-waste-disposal-approved-document-h\" target=\"_blank\" rel=\"noopener\">Building Regulations Approved Document H<\/a> \u2014 a document every drainage engineer working on UK new-build sites should have to hand.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Geocellular vs Concrete Attenuation Tanks Compared<\/h2>\n\n\n\n<div class=\"wp-block-uagb-image aligncenter uagb-block-d5e6f7a8 wp-block-uagb-image--layout-default wp-block-uagb-image--effect-static wp-block-uagb-image--align-center\"><figure class=\"wp-block-uagb-image__figure\"><img decoding=\"async\" srcset=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-installation-sidefill-2.png ,https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-installation-sidefill-2.png 780w, https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-installation-sidefill-2.png 360w\" sizes=\"auto, (max-width: 480px) 150px\" src=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-installation-sidefill-2.png\" alt=\"Geocellular attenuation tank installation showing Class 6N granular sidefill being compacted around polypropylene modules with geotextile separation layer\" class=\"uag-image-8269\" width=\"806\" height=\"915\" title=\"how-does-attenuation-tank-work-installation-sidefill\" loading=\"lazy\" role=\"img\"\/><\/figure><\/div>\n\n\n\n<p><strong>Geocellular modules<\/strong> (PP or PVC) are the choice for around 90% of all UK residential and commercial <strong>attenuation tanks<\/strong>. The <strong>void ratio<\/strong> is 95 to 97%, modules are lightweight at 7 to 12.5 kg per unit, and they can be hand assembled to any plan geometry.<\/p>\n\n\n\n<p>However \u2014 that 95% <strong>void ratio<\/strong>? It\u2019s a gross figure. The structural displacement of plastic columns and beams takes up 3 to 5% of the volume. <strong>CIRIA C753<\/strong> (2015) recommends a 10% silt allowance for future sediment build-up. Add in freeboard and you are looking at a net effective void ratio of 82 to 87%. Still great compared to concrete, but not 95%.<\/p>\n\n\n\n<p><strong>Precast concrete<\/strong> is the clear winner at heavy infrastructure sites, HGV yards or where cover depth is restricted to less than 500 mm. Concrete tanks cope with deep burial and high point loads without engineered backfill \u2014 but at the expense of cost, weight and careful joint sealing.<\/p>\n\n\n\n<p>For a detailed side-by-side engineering breakdown, see our <a href=\"\/concrete-vs-plastic-attenuation-tank\/\">concrete vs plastic attenuation tank<\/a> comparison covering structural performance, load ratings and whole-life cost.<\/p>\n\n\n\n<figure class=\"wp-block-table is-style-stripes\"><table class=\"has-fixed-layout\"><thead><tr><th>System Type<\/th><th>Material Cost (per m\u00b3)<\/th><th>Installed Cost (per m\u00b3)<\/th><th>Void Ratio<\/th><th>Best Application<\/th><\/tr><\/thead><tbody><tr><td>Geocellular (PP)<\/td><td>\u00a380 to \u00a3150<\/td><td>\u00a3200 to \u00a3350<\/td><td>95% gross, ~85% net<\/td><td>Standard residential and commercial<\/td><\/tr><tr><td>Precast concrete<\/td><td>\u00a3450 to \u00a3520<\/td><td>\u00a3400 to \u00a3600<\/td><td>50 to 65%<\/td><td>HGV areas, shallow cover, deep burial<\/td><\/tr><tr><td>Large diameter pipes<\/td><td>Variable<\/td><td>\u00a3300 to \u00a3500<\/td><td>75 to 85%<\/td><td>Linear projects, highways<\/td><\/tr><tr><td>GRP tanks<\/td><td>\u00a3200 to \u00a3350<\/td><td>\u00a3300 to \u00a3500<\/td><td>85 to 90%<\/td><td>Contaminated land, chemical resistance<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\">What Is the Difference Between an Attenuation Tank and a Soakaway?<\/h2>\n\n\n\n<p>This is the question we get asked the most. They both sit in the ground, both deal with surface water and both can use <strong>geocellular<\/strong> crates, but they do very different things.<\/p>\n\n\n\n<p>An <strong>attenuation tank<\/strong> is a sealed system: surface water runoff is collected, stored and released gradually through a flow control device into a watercourse or sewer. The tank is wrapped in a geomembrane (usually HDPE 0.5 to 1.0 mm) that seals everything except where the outlet pipe exits.<\/p>\n\n\n\n<p>A soakaway is a permeable system: surface water is collected and allowed to permeate into the surrounding ground through infiltration. The crates are wrapped in geotextile, not geomembrane, and there is no <strong>flow control<\/strong> device because the ground itself is the drain.<\/p>\n\n\n\n<p>What differentiates them is the <strong>BRE 365<\/strong> decision. If the percolation test indicates adequate infiltration and low groundwater, use a soakaway. If the ground does not absorb enough water, or groundwater is too high, use an <strong>attenuation tank<\/strong> with controlled discharge under the <a href=\"https:\/\/www.legislation.gov.uk\/ukpga\/2010\/29\/contents\" target=\"_blank\" rel=\"noopener\">Flood and Water Management Act 2010<\/a>.<\/p>\n\n\n\n<p>For a detailed site-specific comparison \u2014 including when each system satisfies <strong>LLFA<\/strong> requirements \u2014 read the full <a href=\"\/attenuation-tank-vs-soakaway-uk-drainage-comparison\/\">attenuation tank vs soakaway comparison<\/a>.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-style-default is-layout-flow wp-block-quote-is-layout-flow\">\n<p><em><strong>Warning:<\/strong> Pay attention to vent pipes. When water rushes into an attenuation tank, air has to escape. Without a vent pipe to the inlet chamber or the tank top, air will be trapped, pressurise and blow the manhole covers off. An inexpensive insurance against a dangerous failure mode.<\/em><\/p>\n<\/blockquote>\n\n\n\n<h2 class=\"wp-block-heading\">Common Attenuation Tank Problems and How to Avoid Them<\/h2>\n\n\n\n<div class=\"wp-block-uagb-image uagb-block-b9c0d1e2 wp-block-uagb-image--layout-default wp-block-uagb-image--effect-static wp-block-uagb-image--align-none\"><figure class=\"wp-block-uagb-image__figure\"><img decoding=\"async\" srcset=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-climate-change-allowances-2-1024x559.png ,https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-climate-change-allowances-2.png 780w, https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-climate-change-allowances-2.png 360w\" sizes=\"auto, (max-width: 480px) 150px\" src=\"https:\/\/spcdn.shortpixel.ai\/spio\/ret_img,q_cdnize,to_auto,s_webp:avif\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-climate-change-allowances-2-1024x559.png\" alt=\"UK Environment Agency climate change storage allowances for attenuation tank design showing 2050s and 2070s epoch uplift percentages\" class=\"uag-image-8270\" width=\"1408\" height=\"768\" title=\"how-does-attenuation-tank-work-climate-change-allowances\" loading=\"lazy\" role=\"img\"\/><\/figure><\/div>\n\n\n\n<p>A great deal of <strong>attenuation tank<\/strong> failures are due to installation issues rather than product defects. We\u2019ve supplied <strong>geocellular<\/strong> modules to hundreds of UK projects and the failures we see are almost always to do with what occurred on site rather than what left the factory.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Clay Backfill Collapse, West Midlands<\/h3>\n\n\n\n<p>A commercial car park project in the West Midlands called for <strong>geocellular<\/strong> attenuation crates, 85 m\u00b3 storage in total. Three months upon completion, the surface above the tank had sagged 40 mm. We found that the contractor had used as-dug clay for the sidefill instead of appropriate granular materials. The clay expanded when it absorbed water, lost its shear capacity and did not provide the lateral passive earth pressure that <strong>geocellular<\/strong> modules require. The modules buckled inward.<\/p>\n\n\n\n<p>Remediation cost: full excavation and backfill replacement. Roughly \u00a318,000 of extra works, on top of a \u00a312,000 original installation. Advice: never backfill around <strong>geocellular<\/strong> tanks with clay. Use Type 1 MOT sub-base or 6N graded stone, compacted in 300 mm lifts.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Buoyancy Failure, Southeast England<\/h3>\n\n\n\n<p>A residential site in the Maidstone area commissioned an <strong>attenuation tank<\/strong> of 40 m\u00b3 storage, wrapped in HDPE geomembrane. Heavy overnight rain raised the water table and flooded the surrounding ground. By morning the tank had floated out of the excavation, breaking all pipe connections.<\/p>\n\n\n\n<p>Cause: no buoyancy calculation was carried out. A plastic <strong>geocellular<\/strong> chamber wrapped in impermeable membrane is, by definition, a sealed vessel \u2014 buoyant in saturated ground. The remedy requires 0.5 to 1 m of overburden weight or suitable mechanical ground anchors.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-style-default is-layout-flow wp-block-quote-is-layout-flow\">\n<p><em><strong>Pro Tip:<\/strong> Do a buoyancy check before you lock in cover depth. If groundwater can reach the tank at any time of the year, you need anti-flotation measures. This is a <strong>SuDS<\/strong> design requirement from <strong>CIRIA C753<\/strong> (2015), section 26.<\/em><\/p>\n<\/blockquote>\n\n\n\n<p>The <a href=\"\/blog\/attenuation-tank-installation-guide\/\">step-by-step installation process<\/a> covers buoyancy calculations, cover depth rules and backfill specification in full \u2014 worth reading before any geocellular scheme goes to ground.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">How Long Do Attenuation Tanks Really Last<\/h2>\n\n\n\n<p>Manufacturers quote design lives of 50 to 100 years. That number comes from accelerated creep tests on the polypropylene and, in the laboratory, it is justified. In practice, it is a different matter.<\/p>\n\n\n\n<p>Siltation kills capacity quicker and earlier than structural failure. An estate in Essex flooded two years after completion. The \u201csilt trap\u201d was actually just an uncleared catchpit. When the <strong>attenuation tank<\/strong> was checked, some 60% of the void space was filled with silt \u2014 half the storage space lost. The structure was fine. The maintenance programme was non-existent.<\/p>\n\n\n\n<p>Without a maintenance programme, a <strong>geocellular attenuation tank<\/strong> will operate for 20 to 25 years before siltation reduces storage capacity below design volumes. That is a management failure, not a product failure. It can easily be avoided by regular inspection and jetting.<\/p>\n\n\n\n<p>Inspectability is vital. Current systems from GRAF (EcoBloc Inspect) and Polypipe (Polystorm Inspect) include dedicated inspection tunnels that match with manholes for jetting and CCTV survey. Early <strong>geocellular<\/strong> systems did not have internal access for cleaning. Once full of silt, the only way to fix the system was to excavate the entire tank and rebuild it.<\/p>\n\n\n\n<p>Thermoplastic creep is the other long-lived issue. All polypropylene products will slowly deform under continuous constant load. Reputed manufacturers test to <a href=\"https:\/\/www.bsigroup.com\/en-GB\/standards\/bs-en-iso-899-1\/\" target=\"_blank\" rel=\"noopener\">BS EN ISO 899-1<\/a> and publish creep data for 50-year duration. If a supplier cannot provide this data, the design life should be questioned.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-style-default is-layout-flow wp-block-quote-is-layout-flow\">\n<p><em><strong>Pro Tip:<\/strong> Buy upstream pre-treatment. Hydrodynamic separators upstream of the <strong>attenuation tank<\/strong> will trap silt, hydrocarbons and debris before they enter the storage volume. It\u2019s the best single investment you can make to prolong the useful life of an attenuation tank.<\/em><\/p>\n<\/blockquote>\n\n\n\n<p>Our <a href=\"\/geocellular-attenuation-tanks-guide\/\">geocellular attenuation tanks<\/a> page lists the inspection-access variants we supply, along with maintenance interval guidance for adoptable <strong>SuDS<\/strong> schemes.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Frequently Asked Questions<\/h2>\n\n\n\n<div class=\"schema-faq wp-block-yoast-faq-block\"><div class=\"schema-faq-section\" id=\"faq-question-1743000001000\"><strong class=\"schema-faq-question\">What is an attenuation tank used for?<\/strong> <p class=\"schema-faq-answer\">An attenuation tank stores surface water runoff from developed sites and releases it at a controlled rate, typically matching greenfield runoff rates of 2 to 8 l\/s per hectare. It prevents downstream flooding and sewer surcharging by reducing peak flow from impervious surfaces like roofs and car parks. Under the Flood and Water Management Act 2010, most new UK developments require attenuation as part of their SuDS strategy.<\/p> <\/div> <div class=\"schema-faq-section\" id=\"faq-question-1743000002000\"><strong class=\"schema-faq-question\">How much does an attenuation tank cost?<\/strong> <p class=\"schema-faq-answer\">Geocellular attenuation tanks cost between \u00a3200 and \u00a3350 per cubic metre installed, including excavation, geomembrane, geotextile, backfill, and flow control. Precast concrete systems range from \u00a3400 to \u00a3600 per m\u00b3 installed. A typical residential scheme needing 30 m\u00b3 of storage will cost roughly \u00a36,000 to \u00a310,500 for geocellular, or \u00a312,000 to \u00a318,000 for concrete. The flow control device adds \u00a380 to \u00a32,500 depending on type.<\/p> <\/div> <div class=\"schema-faq-section\" id=\"faq-question-1743000003000\"><strong class=\"schema-faq-question\">How much attenuation storage do I need?<\/strong> <p class=\"schema-faq-answer\">Storage volume depends on catchment area, impervious percentage, greenfield runoff rate, and climate change allowance. A 0.25 ha residential site with 70% impervious area and a 2070s upper end climate change allowance (+40%) typically requires 40 to 65 m\u00b3 of attenuation storage. You can\u2019t calculate this by hand. Use drainage modelling software like MicroDrainage and run storms from 15 minutes to 48 hours to find the critical storm duration.<\/p> <\/div> <div class=\"schema-faq-section\" id=\"faq-question-1743000004000\"><strong class=\"schema-faq-question\">How is an attenuation tank installed?<\/strong> <p class=\"schema-faq-answer\">Installation follows six stages: excavation to formation level, lay and compact Type 1 sub-base (150 mm minimum), place geotextile separation layer, assemble geocellular modules, wrap in HDPE geomembrane with hot-welded seams, and backfill with granular material compacted in 300 mm lifts. Connect inlet and outlet pipes, install the flow control device, and fit vent pipes. The entire process takes 2 to 5 days for a standard residential system.<\/p> <\/div> <div class=\"schema-faq-section\" id=\"faq-question-1743000005000\"><strong class=\"schema-faq-question\">Who approves attenuation tank designs in the UK?<\/strong> <p class=\"schema-faq-answer\">The Lead Local Flood Authority (LLFA) approves surface water drainage designs for new developments under the Flood and Water Management Act 2010, Schedule 3. The LLFA checks compliance with local SuDS policy, BS EN 752 (2017) for drain and sewer design, and CIRIA C753 (2015) for SuDS technical standards. For connections to public sewers, you also need Section 106 or Section 104 agreement from the relevant water company.<\/p> <\/div> <\/div>\n\n\n\n<h2 class=\"wp-block-heading\">Next Steps<\/h2>\n\n\n\n<p>Getting the design right means specifying the correct tank volume, choosing the appropriate flow control device, using the right backfill, and building in a maintenance plan from day one. An <strong>attenuation tank<\/strong> specified to the right volume, with a vortex flow control, inspectable <strong>geocellular<\/strong> modules, pre-treatment upstream, and a maintenance plan, can do the job for the whole design life.<\/p>\n\n\n\n<p>If you need us to size an <strong>attenuation tank<\/strong> for a new project, just let us know your site area, impervious percent and <strong>LLFA<\/strong> discharge requirements. We\u2019ll verify the <strong>geocellular<\/strong> module specification, suggest a <strong>flow control<\/strong> device and provide your drainage consultant with the technical datasheets they need for submission.<\/p>\n\n\n\n<p>Browse our range of <a href=\"\/products\/geocellular-stormwater-modules\/\">geocellular stormwater modules<\/a> or explore our <a href=\"\/solutions\/subsurface-stormwater-management-systems\/\">subsurface stormwater management systems<\/a> solution page for technical specifications and project application data.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-style-default is-layout-flow wp-block-quote-is-layout-flow\">\n<p><em>Disclaimer: Case studies are illustrative examples based on typical project scenarios. Always consult a qualified drainage engineer and your LLFA prior to finalising drainage designs. Cost data reflects industry benchmark ranges and should not be used to estimate project costs without site inspection.<\/em><\/p>\n<\/blockquote>\n\n\n\n<script type=\"application\/ld+json\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"TechArticle\",\"@id\":\"https:\/\/aquarainwater.com\/blog\/how-does-attenuation-tank-work\/#article\",\"headline\":\"How an Attenuation Tank Works: Mechanism, Flow Control and UK Sizing\",\"description\":\"Learn how attenuation tanks work: three-stage mechanism, vortex flow control vs orifice, UK sizing with FEH, costs and common installation problems.\",\"proficiencyLevel\":\"Expert\",\"about\":[{\"@type\":\"Thing\",\"name\":\"Attenuation tank\",\"sameAs\":\"https:\/\/en.wikipedia.org\/wiki\/Stormwater_detention_vault\"},{\"@type\":\"Thing\",\"name\":\"Sustainable drainage systems\",\"sameAs\":\"https:\/\/en.wikipedia.org\/wiki\/Sustainable_drainage_system\"}],\"mentions\":[{\"@type\":\"Thing\",\"name\":\"BRE 365\",\"sameAs\":\"https:\/\/www.susdrain.org\/delivering-suds\/using-suds\/suds-components\/infiltration\/soakaway-design.html\"},{\"@type\":\"Thing\",\"name\":\"CIRIA C753\",\"sameAs\":\"https:\/\/www.susdrain.org\/delivering-suds\/using-suds\/the-suds-manual-c753.html\"},{\"@type\":\"Thing\",\"name\":\"Flood Estimation Handbook\",\"sameAs\":\"https:\/\/en.wikipedia.org\/wiki\/Flood_Estimation_Handbook\"},{\"@type\":\"Legislation\",\"name\":\"Flood and Water Management Act 2010\",\"sameAs\":\"https:\/\/en.wikipedia.org\/wiki\/Flood_and_Water_Management_Act_2010\"}],\"speakable\":{\"@type\":\"SpeakableSpecification\",\"cssSelector\":[\".schema-faq-answer\",\".geo-definition\"]},\"author\":{\"@type\":\"Organization\",\"@id\":\"https:\/\/aquarainwater.com\/#organization\",\"name\":\"AQUA Rain Water Solutions\",\"url\":\"https:\/\/aquarainwater.com\/about\/\"},\"publisher\":{\"@type\":\"Organization\",\"@id\":\"https:\/\/aquarainwater.com\/#organization\"},\"datePublished\":\"2026-02-17\",\"dateModified\":\"2026-03-27\",\"mainEntityOfPage\":{\"@type\":\"WebPage\",\"@id\":\"https:\/\/aquarainwater.com\/blog\/how-does-attenuation-tank-work\/\"},\"image\":{\"@type\":\"ImageObject\",\"url\":\"\"}},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/aquarainwater.com\/blog\/how-does-attenuation-tank-work\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\/\/aquarainwater.com\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Blog\",\"item\":\"https:\/\/aquarainwater.com\/blog\/\"},{\"@type\":\"ListItem\",\"position\":3,\"name\":\"How an Attenuation Tank Works: Mechanism, Flow Control and UK Sizing\",\"item\":\"https:\/\/aquarainwater.com\/blog\/how-does-attenuation-tank-work\/\"}]},{\"@type\":\"Organization\",\"@id\":\"https:\/\/aquarainwater.com\/#organization\",\"name\":\"AQUA Rain Water Solutions\",\"url\":\"https:\/\/aquarainwater.com\",\"sameAs\":[\"https:\/\/www.linkedin.com\/company\/aquarainwater\",\"https:\/\/www.facebook.com\/aquarainwater\"],\"knowsAbout\":[\"Stormwater Management\",\"Geocellular Drainage Systems\",\"SuDS Design\",\"Attenuation Tank Engineering\",\"Ground Reinforcement\"],\"areaServed\":[{\"@type\":\"Country\",\"name\":\"United Kingdom\"},{\"@type\":\"Country\",\"name\":\"Ireland\"},{\"@type\":\"Country\",\"name\":\"Netherlands\"},{\"@type\":\"Country\",\"name\":\"Germany\"},{\"@type\":\"Country\",\"name\":\"Belgium\"}]}]}<\/script>\n","protected":false},"excerpt":{"rendered":"<p>Apprenez comment fonctionnent les r\u00e9servoirs d'att\u00e9nuation : m\u00e9canisme \u00e0 trois \u00e9tages, contr\u00f4le du d\u00e9bit par vortex ou par orifice, dimensionnement du Royaume-Uni avec FEH, co\u00fbts et probl\u00e8mes d'installation courants.<\/p>","protected":false},"author":1,"featured_media":7670,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"_uag_custom_page_level_css":"","_kad_blocks_custom_css":"","_kad_blocks_head_custom_js":"","_kad_blocks_body_custom_js":"","_kad_blocks_footer_custom_js":"","site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"set","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"footnotes":""},"categories":[107],"tags":[],"class_list":["post-7663","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v26.9 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>How Does an Attenuation Tank Work? | UK Expert Guide<\/title>\n<meta name=\"description\" content=\"Learn how attenuation tanks work: three-stage mechanism, vortex flow control vs orifice, UK sizing with FEH, costs and common installation problems.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/aquarainwater.com\/fr\/how-does-attenuation-tank-work\/\" \/>\n<meta property=\"og:locale\" content=\"fr_FR\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"How Does an Attenuation Tank Work? | UK Expert Guide\" \/>\n<meta property=\"og:description\" content=\"Learn how attenuation tanks work: three-stage mechanism, vortex flow control vs orifice, UK sizing with FEH, costs and common installation problems.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/aquarainwater.com\/fr\/how-does-attenuation-tank-work\/\" \/>\n<meta property=\"og:site_name\" content=\"Aquarainwater\" \/>\n<meta property=\"article:published_time\" content=\"2026-02-17T15:58:01+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2026-03-27T16:15:44+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured.png\" \/>\n\t<meta property=\"og:image:width\" content=\"1607\" \/>\n\t<meta property=\"og:image:height\" content=\"1200\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/png\" \/>\n<meta name=\"author\" content=\"aquarainwater\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"\u00c9crit par\" \/>\n\t<meta name=\"twitter:data1\" content=\"aquarainwater\" \/>\n\t<meta name=\"twitter:label2\" content=\"Dur\u00e9e de lecture estim\u00e9e\" \/>\n\t<meta name=\"twitter:data2\" content=\"13 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/\"},\"author\":{\"name\":\"aquarainwater\",\"@id\":\"https:\/\/aquarainwater.com\/#\/schema\/person\/f518511845b1786db5ab0234f85c5ce2\"},\"headline\":\"How an Attenuation Tank Works: Mechanism, Flow Control and UK Sizing\",\"datePublished\":\"2026-02-17T15:58:01+00:00\",\"dateModified\":\"2026-03-27T16:15:44+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/\"},\"wordCount\":2706,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\/\/aquarainwater.com\/#organization\"},\"image\":{\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured.png\",\"articleSection\":[\"Blog\"],\"inLanguage\":\"fr-FR\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#respond\"]}]},{\"@type\":[\"WebPage\",\"FAQPage\"],\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/\",\"url\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/\",\"name\":\"How Does an Attenuation Tank Work? | UK Expert Guide\",\"isPartOf\":{\"@id\":\"https:\/\/aquarainwater.com\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured.png\",\"datePublished\":\"2026-02-17T15:58:01+00:00\",\"dateModified\":\"2026-03-27T16:15:44+00:00\",\"description\":\"Learn how attenuation tanks work: three-stage mechanism, vortex flow control vs orifice, UK sizing with FEH, costs and common installation problems.\",\"breadcrumb\":{\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#breadcrumb\"},\"mainEntity\":[{\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000001000\"},{\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000002000\"},{\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000003000\"},{\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000004000\"},{\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000005000\"}],\"inLanguage\":\"fr-FR\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"fr-FR\",\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#primaryimage\",\"url\":\"https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured.png\",\"contentUrl\":\"https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured.png\",\"width\":1607,\"height\":1200,\"caption\":\"Cutaway diagram showing how an attenuation tank works underground with geocellular modules, water flow arrows, and flow control device\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"HOME\",\"item\":\"https:\/\/aquarainwater.com\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Blog\",\"item\":\"https:\/\/aquarainwater.com\/category\/blog\/\"},{\"@type\":\"ListItem\",\"position\":3,\"name\":\"How an Attenuation Tank Works: Mechanism, Flow Control and UK Sizing\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/aquarainwater.com\/#website\",\"url\":\"https:\/\/aquarainwater.com\/\",\"name\":\"Underground Stormwater Detention & Infiltration Solutions Expert | Flood Mitigation & LID\",\"description\":\"\",\"publisher\":{\"@id\":\"https:\/\/aquarainwater.com\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/aquarainwater.com\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"fr-FR\"},{\"@type\":\"Organization\",\"@id\":\"https:\/\/aquarainwater.com\/#organization\",\"name\":\"ARW Stormwater Management\",\"url\":\"https:\/\/aquarainwater.com\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"fr-FR\",\"@id\":\"https:\/\/aquarainwater.com\/#\/schema\/logo\/image\/\",\"url\":\"https:\/\/aquarainwater.com\/wp-content\/uploads\/2025\/09\/cropped-cropped-\u5fae\u4fe1\u56fe\u7247_20250827165723_16_579.png\",\"contentUrl\":\"https:\/\/aquarainwater.com\/wp-content\/uploads\/2025\/09\/cropped-cropped-\u5fae\u4fe1\u56fe\u7247_20250827165723_16_579.png\",\"width\":514,\"height\":224,\"caption\":\"ARW Stormwater Management\"},\"image\":{\"@id\":\"https:\/\/aquarainwater.com\/#\/schema\/logo\/image\/\"},\"sameAs\":[\"https:\/\/www.linkedin.cn\/incareer\/company\/arw-stormwater-management\/\",\"https:\/\/wa.me\/85267102428\"]},{\"@type\":\"Person\",\"@id\":\"https:\/\/aquarainwater.com\/#\/schema\/person\/f518511845b1786db5ab0234f85c5ce2\",\"name\":\"aquarainwater\",\"sameAs\":[\"https:\/\/aquarainwater.com\"],\"url\":\"https:\/\/aquarainwater.com\/fr\/author\/hong\/\"},{\"@type\":\"Question\",\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000001000\",\"position\":1,\"url\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000001000\",\"name\":\"What is an attenuation tank used for?\",\"answerCount\":1,\"acceptedAnswer\":{\"@type\":\"Answer\",\"text\":\"An attenuation tank stores surface water runoff from developed sites and releases it at a controlled rate, typically matching greenfield runoff rates of 2 to 8 l\/s per hectare. It prevents downstream flooding and sewer surcharging by reducing peak flow from impervious surfaces like roofs and car parks. Under the Flood and Water Management Act 2010, most new UK developments require attenuation as part of their SuDS strategy.\",\"inLanguage\":\"fr-FR\"},\"inLanguage\":\"fr-FR\"},{\"@type\":\"Question\",\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000002000\",\"position\":2,\"url\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000002000\",\"name\":\"How much does an attenuation tank cost?\",\"answerCount\":1,\"acceptedAnswer\":{\"@type\":\"Answer\",\"text\":\"Geocellular attenuation tanks cost between \u00a3200 and \u00a3350 per cubic metre installed, including excavation, geomembrane, geotextile, backfill, and flow control. Precast concrete systems range from \u00a3400 to \u00a3600 per m\u00b3 installed. A typical residential scheme needing 30 m\u00b3 of storage will cost roughly \u00a36,000 to \u00a310,500 for geocellular, or \u00a312,000 to \u00a318,000 for concrete. The flow control device adds \u00a380 to \u00a32,500 depending on type.\",\"inLanguage\":\"fr-FR\"},\"inLanguage\":\"fr-FR\"},{\"@type\":\"Question\",\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000003000\",\"position\":3,\"url\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000003000\",\"name\":\"How much attenuation storage do I need?\",\"answerCount\":1,\"acceptedAnswer\":{\"@type\":\"Answer\",\"text\":\"Storage volume depends on catchment area, impervious percentage, greenfield runoff rate, and climate change allowance. A 0.25 ha residential site with 70% impervious area and a 2070s upper end climate change allowance (+40%) typically requires 40 to 65 m\u00b3 of attenuation storage. You can't calculate this by hand. Use drainage modelling software like MicroDrainage and run storms from 15 minutes to 48 hours to find the critical storm duration.\",\"inLanguage\":\"fr-FR\"},\"inLanguage\":\"fr-FR\"},{\"@type\":\"Question\",\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000004000\",\"position\":4,\"url\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000004000\",\"name\":\"How is an attenuation tank installed?\",\"answerCount\":1,\"acceptedAnswer\":{\"@type\":\"Answer\",\"text\":\"Installation follows six stages: excavation to formation level, lay and compact Type 1 sub-base (150 mm minimum), place geotextile separation layer, assemble geocellular modules, wrap in HDPE geomembrane with hot-welded seams, and backfill with granular material compacted in 300 mm lifts. Connect inlet and outlet pipes, install the flow control device, and fit vent pipes. The entire process takes 2 to 5 days for a standard residential system.\",\"inLanguage\":\"fr-FR\"},\"inLanguage\":\"fr-FR\"},{\"@type\":\"Question\",\"@id\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000005000\",\"position\":5,\"url\":\"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000005000\",\"name\":\"Who approves attenuation tank designs in the UK?\",\"answerCount\":1,\"acceptedAnswer\":{\"@type\":\"Answer\",\"text\":\"The Lead Local Flood Authority (LLFA) approves surface water drainage designs for new developments under the Flood and Water Management Act 2010, Schedule 3. The LLFA checks compliance with local SuDS policy, BS EN 752 (2017) for drain and sewer design, and CIRIA C753 (2015) for SuDS technical standards. For connections to public sewers, you also need Section 106 or Section 104 agreement from the relevant water company.\",\"inLanguage\":\"fr-FR\"},\"inLanguage\":\"fr-FR\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Comment fonctionne un r\u00e9servoir d'att\u00e9nuation ? | Guide de l'expert","description":"Apprenez comment fonctionnent les r\u00e9servoirs d'att\u00e9nuation : m\u00e9canisme \u00e0 trois \u00e9tages, contr\u00f4le du d\u00e9bit par vortex ou par orifice, dimensionnement du Royaume-Uni avec FEH, co\u00fbts et probl\u00e8mes d'installation courants.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/aquarainwater.com\/fr\/how-does-attenuation-tank-work\/","og_locale":"fr_FR","og_type":"article","og_title":"How Does an Attenuation Tank Work? | UK Expert Guide","og_description":"Learn how attenuation tanks work: three-stage mechanism, vortex flow control vs orifice, UK sizing with FEH, costs and common installation problems.","og_url":"https:\/\/aquarainwater.com\/fr\/how-does-attenuation-tank-work\/","og_site_name":"Aquarainwater","article_published_time":"2026-02-17T15:58:01+00:00","article_modified_time":"2026-03-27T16:15:44+00:00","og_image":[{"width":1607,"height":1200,"url":"https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured.png","type":"image\/png"}],"author":"aquarainwater","twitter_card":"summary_large_image","twitter_misc":{"\u00c9crit par":"aquarainwater","Dur\u00e9e de lecture estim\u00e9e":"13 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#article","isPartOf":{"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/"},"author":{"name":"aquarainwater","@id":"https:\/\/aquarainwater.com\/#\/schema\/person\/f518511845b1786db5ab0234f85c5ce2"},"headline":"How an Attenuation Tank Works: Mechanism, Flow Control and UK Sizing","datePublished":"2026-02-17T15:58:01+00:00","dateModified":"2026-03-27T16:15:44+00:00","mainEntityOfPage":{"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/"},"wordCount":2706,"commentCount":0,"publisher":{"@id":"https:\/\/aquarainwater.com\/#organization"},"image":{"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#primaryimage"},"thumbnailUrl":"https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured.png","articleSection":["Blog"],"inLanguage":"fr-FR","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#respond"]}]},{"@type":["WebPage","FAQPage"],"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/","url":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/","name":"Comment fonctionne un r\u00e9servoir d'att\u00e9nuation ? | Guide de l'expert","isPartOf":{"@id":"https:\/\/aquarainwater.com\/#website"},"primaryImageOfPage":{"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#primaryimage"},"image":{"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#primaryimage"},"thumbnailUrl":"https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured.png","datePublished":"2026-02-17T15:58:01+00:00","dateModified":"2026-03-27T16:15:44+00:00","description":"Apprenez comment fonctionnent les r\u00e9servoirs d'att\u00e9nuation : m\u00e9canisme \u00e0 trois \u00e9tages, contr\u00f4le du d\u00e9bit par vortex ou par orifice, dimensionnement du Royaume-Uni avec FEH, co\u00fbts et probl\u00e8mes d'installation courants.","breadcrumb":{"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#breadcrumb"},"mainEntity":[{"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000001000"},{"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000002000"},{"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000003000"},{"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000004000"},{"@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000005000"}],"inLanguage":"fr-FR","potentialAction":[{"@type":"ReadAction","target":["https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/"]}]},{"@type":"ImageObject","inLanguage":"fr-FR","@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#primaryimage","url":"https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured.png","contentUrl":"https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured.png","width":1607,"height":1200,"caption":"Cutaway diagram showing how an attenuation tank works underground with geocellular modules, water flow arrows, and flow control device"},{"@type":"BreadcrumbList","@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"HOME","item":"https:\/\/aquarainwater.com\/"},{"@type":"ListItem","position":2,"name":"Blog","item":"https:\/\/aquarainwater.com\/category\/blog\/"},{"@type":"ListItem","position":3,"name":"How an Attenuation Tank Works: Mechanism, Flow Control and UK Sizing"}]},{"@type":"WebSite","@id":"https:\/\/aquarainwater.com\/#website","url":"https:\/\/aquarainwater.com\/","name":"Expert en solutions de r\u00e9tention et d'infiltration des eaux pluviales souterraines - Att\u00e9nuation des inondations et am\u00e9nagement du territoire","description":"","publisher":{"@id":"https:\/\/aquarainwater.com\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/aquarainwater.com\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"fr-FR"},{"@type":"Organization","@id":"https:\/\/aquarainwater.com\/#organization","name":"Gestion des eaux pluviales ARW","url":"https:\/\/aquarainwater.com\/","logo":{"@type":"ImageObject","inLanguage":"fr-FR","@id":"https:\/\/aquarainwater.com\/#\/schema\/logo\/image\/","url":"https:\/\/aquarainwater.com\/wp-content\/uploads\/2025\/09\/cropped-cropped-\u5fae\u4fe1\u56fe\u7247_20250827165723_16_579.png","contentUrl":"https:\/\/aquarainwater.com\/wp-content\/uploads\/2025\/09\/cropped-cropped-\u5fae\u4fe1\u56fe\u7247_20250827165723_16_579.png","width":514,"height":224,"caption":"ARW Stormwater Management"},"image":{"@id":"https:\/\/aquarainwater.com\/#\/schema\/logo\/image\/"},"sameAs":["https:\/\/www.linkedin.cn\/incareer\/company\/arw-stormwater-management\/","https:\/\/wa.me\/85267102428"]},{"@type":"Person","@id":"https:\/\/aquarainwater.com\/#\/schema\/person\/f518511845b1786db5ab0234f85c5ce2","name":"eau de mer","sameAs":["https:\/\/aquarainwater.com"],"url":"https:\/\/aquarainwater.com\/fr\/author\/hong\/"},{"@type":"Question","@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000001000","position":1,"url":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000001000","name":"\u00c0 quoi sert un r\u00e9servoir d'att\u00e9nuation ?","answerCount":1,"acceptedAnswer":{"@type":"Answer","text":"An attenuation tank stores surface water runoff from developed sites and releases it at a controlled rate, typically matching greenfield runoff rates of 2 to 8 l\/s per hectare. It prevents downstream flooding and sewer surcharging by reducing peak flow from impervious surfaces like roofs and car parks. Under the Flood and Water Management Act 2010, most new UK developments require attenuation as part of their SuDS strategy.","inLanguage":"fr-FR"},"inLanguage":"fr-FR"},{"@type":"Question","@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000002000","position":2,"url":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000002000","name":"Quel est le co\u00fbt d'un r\u00e9servoir d'att\u00e9nuation ?","answerCount":1,"acceptedAnswer":{"@type":"Answer","text":"Geocellular attenuation tanks cost between \u00a3200 and \u00a3350 per cubic metre installed, including excavation, geomembrane, geotextile, backfill, and flow control. Precast concrete systems range from \u00a3400 to \u00a3600 per m\u00b3 installed. A typical residential scheme needing 30 m\u00b3 of storage will cost roughly \u00a36,000 to \u00a310,500 for geocellular, or \u00a312,000 to \u00a318,000 for concrete. The flow control device adds \u00a380 to \u00a32,500 depending on type.","inLanguage":"fr-FR"},"inLanguage":"fr-FR"},{"@type":"Question","@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000003000","position":3,"url":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000003000","name":"De quelle quantit\u00e9 de stockage d'att\u00e9nuation ai-je besoin ?","answerCount":1,"acceptedAnswer":{"@type":"Answer","text":"Storage volume depends on catchment area, impervious percentage, greenfield runoff rate, and climate change allowance. A 0.25 ha residential site with 70% impervious area and a 2070s upper end climate change allowance (+40%) typically requires 40 to 65 m\u00b3 of attenuation storage. You can't calculate this by hand. Use drainage modelling software like MicroDrainage and run storms from 15 minutes to 48 hours to find the critical storm duration.","inLanguage":"fr-FR"},"inLanguage":"fr-FR"},{"@type":"Question","@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000004000","position":4,"url":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000004000","name":"Comment un r\u00e9servoir d'att\u00e9nuation est-il install\u00e9 ?","answerCount":1,"acceptedAnswer":{"@type":"Answer","text":"Installation follows six stages: excavation to formation level, lay and compact Type 1 sub-base (150 mm minimum), place geotextile separation layer, assemble geocellular modules, wrap in HDPE geomembrane with hot-welded seams, and backfill with granular material compacted in 300 mm lifts. Connect inlet and outlet pipes, install the flow control device, and fit vent pipes. The entire process takes 2 to 5 days for a standard residential system.","inLanguage":"fr-FR"},"inLanguage":"fr-FR"},{"@type":"Question","@id":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000005000","position":5,"url":"https:\/\/aquarainwater.com\/how-does-attenuation-tank-work\/#faq-question-1743000005000","name":"Qui approuve la conception des bassins d'att\u00e9nuation au Royaume-Uni ?","answerCount":1,"acceptedAnswer":{"@type":"Answer","text":"The Lead Local Flood Authority (LLFA) approves surface water drainage designs for new developments under the Flood and Water Management Act 2010, Schedule 3. The LLFA checks compliance with local SuDS policy, BS EN 752 (2017) for drain and sewer design, and CIRIA C753 (2015) for SuDS technical standards. For connections to public sewers, you also need Section 106 or Section 104 agreement from the relevant water company.","inLanguage":"fr-FR"},"inLanguage":"fr-FR"}]}},"taxonomy_info":{"category":[{"value":107,"label":"Blog"}]},"featured_image_src_large":["https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured-1024x765.png",1024,765,true],"author_info":{"display_name":"aquarainwater","author_link":"https:\/\/aquarainwater.com\/fr\/author\/hong\/"},"comment_info":0,"category_info":[{"term_id":107,"name":"Blog","slug":"blog","term_group":0,"term_taxonomy_id":107,"taxonomy":"category","description":"","parent":0,"count":31,"filter":"raw","cat_ID":107,"category_count":31,"category_description":"","cat_name":"Blog","category_nicename":"blog","category_parent":0}],"tag_info":false,"uagb_featured_image_src":{"full":["https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured.png",1607,1200,false],"thumbnail":["https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured-150x150.png",150,150,true],"medium":["https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured-300x224.png",300,224,true],"medium_large":["https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured-768x573.png",768,573,true],"large":["https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured-1024x765.png",1024,765,true],"1536x1536":["https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured-1536x1147.png",1536,1147,true],"2048x2048":["https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured-2048x1529.png",1607,1200,true],"trp-custom-language-flag":["https:\/\/aquarainwater.com\/wp-content\/uploads\/2026\/02\/how-does-attenuation-tank-work-featured-16x12.png",16,12,true]},"uagb_author_info":{"display_name":"aquarainwater","author_link":"https:\/\/aquarainwater.com\/fr\/author\/hong\/"},"uagb_comment_info":0,"uagb_excerpt":"Learn how attenuation tanks work: three-stage mechanism, vortex flow control vs orifice, UK sizing with FEH, costs and common installation problems.","_links":{"self":[{"href":"https:\/\/aquarainwater.com\/fr\/wp-json\/wp\/v2\/posts\/7663","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/aquarainwater.com\/fr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/aquarainwater.com\/fr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/aquarainwater.com\/fr\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/aquarainwater.com\/fr\/wp-json\/wp\/v2\/comments?post=7663"}],"version-history":[{"count":27,"href":"https:\/\/aquarainwater.com\/fr\/wp-json\/wp\/v2\/posts\/7663\/revisions"}],"predecessor-version":[{"id":8271,"href":"https:\/\/aquarainwater.com\/fr\/wp-json\/wp\/v2\/posts\/7663\/revisions\/8271"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/aquarainwater.com\/fr\/wp-json\/wp\/v2\/media\/7670"}],"wp:attachment":[{"href":"https:\/\/aquarainwater.com\/fr\/wp-json\/wp\/v2\/media?parent=7663"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/aquarainwater.com\/fr\/wp-json\/wp\/v2\/categories?post=7663"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/aquarainwater.com\/fr\/wp-json\/wp\/v2\/tags?post=7663"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}